62 FP5/GP5 User’s Manual
Chapter 3 - Programming Features
FP5/GP5 Operation
·MODBUS Frequency Reference Unit (n103, MODBUS Fref Unit)
The frequency reference units from the PLC and in the frequency refer-
ence and output frequency monitors (by communication) are set with
parameter n103. The output frequency resolution of the FP5/GP5
is 0.1Hz. Even if the frequency reference unit is changed to 0.01Hz in
parameter n103, the value in the hundredth digit of the received fre-
quency reference is rounded off internally. When 30,000/100% in units
of 0.1% is selected, the value is rounded off in the same way.
·MODBUS Slave Address (n104, MODBUS Address)
Sets the slave address number. It is necessary to set the address number
so that it will not overlap with the address number of another slave unit
connected on the same transmission line.
Note:To change the values set in parameters n104 to n106 and enable new settings, it is
necessary to cycle power after entering the desired values.
Motor Overload Detection
The FP5/GP5 protects against motor overload with a UL-recog-
nized, built-in electronic thermal overload relay function.
·Motor Rated Current (n033, Motor Rated FLA)
Set to the rated current value shown on the motor nameplate.
Note: setting to 0.0A disables the motor overload protection function.
·Motor overload protection selection (n034, Motor OL Sel)
The electronic thermal overload function estimates motor temperature,
based on inverter output current and time, to protect the motor from
overheating. When the electronic thermal overload relay is activated, an
“oL1” error occurs, shutting OFF the inverter output and preventing
excessive overheating in the motor.
When operating with one inverter connected to one motor, an external
thermal relay is not needed. When operating several motors with one
inverter, install a thermal relay on each motor. In this case, set parame-
ter n034 to “Disabled”.
LED Setting LCD Setting Electronic Thermal Characteristics
0 Disabled Protection disabled
1 STD Motor / 8 min Applied to general-purpose motor,
standard rating (Class 20 overload)
2 STD Motor / 5 min Applied to general-purpose motor,
short time rating (Class 10 overload)
3 INV Motor / 8 min Applied to blower-cooled / inverter duty motor,
standard rating (Class 20 overload)
4 INV Motor / 5 min Applied to blower-cooled / inverter duty motor,
short time rating (Class 10 overload)
efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor
Vedere la pagina 61
1 2 ... 57 58 59 60 61 62 63 64 65 66 67 ... 100 101

Commenti su questo manuale

Nessun commento

Daewoo DTQ-14U5SC podręczniki

Instrukcje obsługi i podręczniki użytkownika dla Telewizory i monitory Daewoo DTQ-14U5SC.
Dostarczamy 1 pdf podręczników Daewoo DTQ-14U5SC do pobrania za darmo według typów dokumentów: Instrukcja Obsługi






Więcej produktów i instrukcji dla Telewizory i monitory Daewoo

Modele Rodzaj dokumentu
DTD-21D6 Instrukcja Użytkownika   IDC4 SOFTWARE - AT Service Group, 8 strony
DTQ-14Q1FS Instrukcja Użytkownika   subasta de walmart martes 28 de octubre del 2014, 1 strony
CML-523BM Instrukcja Obsługi   Daewoo CML-523BM Service manual, 36 strony
DTA-1420MP Instrukcja Użytkownika   Anunturi din 28 noiembrie 2014, 2 strony
DTA-2132P Instrukcja Użytkownika   2 - big country, 182 strony
DTQ 13V5FC Instrukcja Użytkownika   2004 Annual Report - LCATV Field Production, 35 strony
DP-42SM Instrukcja Obsługi   Daewoo DP-42SM Service manual, 124 strony